The manipulation of the application program on the logic system, which can violate the integrity of an SIS, represents the greatest risk. Unlike with “simple” OT components, this can potentially have the most severe consequences for the security of people, the environment, and technical installations. On worksheet NA 163 from the international User Association of Automation Technology in Process Industries (NAMUR), the following three categories are defined in this respect:

In December 2017, the first reports were published on malware that had deliberately manipulated SIS. The perpetrators had gained entry via an engineering station where special software for programming and parameterisation was located. From there, the malware installed searched specifically for connected logic systems from a certain manufacturer and loaded executable code onto them, which manipulated the application program (the logic). The validity check failed due to an error in this code. The security function was then triggered and the attacked system was put into safe mode. Although the attack was not successful, its impact and complexity could have been classified as Category 2 or 3.