+PS-03 Perimeter Protection
---+PS-03.01B
---+PS-03.02B
---+PS-03.03B
---+PS-03.04B
---+PS-03.05B
---+PS-03.06B
---+PS-03.01AC

PS-03 Perimeter Protection

1. Přehled

Název Standard
PS-03.01B

The structural shell of premises and buildings related to the cloud service provided are physically solid and protected by adequate security measures that meet the security requirements of the cloud service provider (cf. PS-01).

PS-03.02B

The security measures are designed to detect and prevent unauthorised access so that the information security of the cloud service is not compromised.

Supplementary information

Security measures for detecting unauthorised access can be security personnel, video surveillance or anti-burglary systems.

PS-03.03B

The outer doors, windows and other construction elements exhibit an appropriate security level so that their combined resistance time withstand a break-in attempt for at least ten minutes in total. This time period applies from the moment an external intruder is detected (e.g. by perimeter surveillance).

Supplementary information

The resistance class RC4 according to DIN EN 1627 stipulates that doors, windows and other components shall withstand a break-in attempt for at least ten minutes. The US standard SD-STD-01.01 Rev.G. is an international equivalent to this standard. However, fulfilling the objective of this criteria does not necessarily imply that those standards have to be fulfilled.

Additionally, the subcriterion demands that all construction elements as a whole lead to a resistance time to break-in attempts for at least ten minutes. Consequently, it does not necessarly demand that all individual construction elements have to fulfil this requirement on their own, provided the combined measures effectively delay an external attack for the required time.

PS-03.04B

The surrounding wall constructions as well as the locking mechanisms meet the associated requirements.

Supplementary information

The resistance class RC4 according to DIN EN 1627 stipulates that doors, windows and other components shall withstand a break-in attempt for at least ten minutes. The US standard SD-STD-01.01 Rev.G. is an international equivalent to this standard. However, fulfilling the objective of this criteria does not necessarily imply that those standards have to be fulfilled.

Additionally, the subcriterion demands that all construction elements as a whole lead to a resistance time to break-in attempts for at least ten minutes. Consequently, it does not necessarly demand that all individual construction elements have to fulfil this requirement on their own, provided the combined measures effectively delay an external attack for the required time.

PS-03.05B

If the construction elements as a whole do not fully meet the associated requirements, compensating controls are implemented to restore the appropriate security level.

Supplementary information

Compensating measures can include additional security layers (e.g. security areas) on the premise, an increased presence of security personnel, video surveillance and anti-burglary systems.

PS-03.06B

Data centre personnel are trained on how to respond effectively to unauthorised ingress or egress attempts.

PS-03.01AC

The security measures installed at the site include permanently present security personnel (at least two individuals), video surveillance and anti-burglary systems.

1.1 Odkazy

1.2 Identifikované požadavky

1.3 Související regulace

2. Identifikované požadavky

Požadavky
Zdroj Požadavek

3. Související regulace

Regulace
Zdroj Regulace