+PE-11 Emergency Power
---+PE-11(01) Alternate Power Supply — Minimal Operational Capability
---+PE-11(02) Alternate Power Supply — Self-contained

PE-11 Emergency Power

Control

Provide an uninterruptible power supply to facilitate [Selection: an orderly shutdown of the system; transition of the system to long-term alternate power] in the event of a primary power source loss.

Discussion

An uninterruptible power supply (UPS) is an electrical system or mechanism that provides emergency power when there is a failure of the main power source. A UPS is typically used to protect computers, data centers, telecommunication equipment, or other electrical equipment where an unexpected power disruption could cause injuries, fatalities, serious mission or business disruption, or loss of data or information. A UPS differs from an emergency power system or backup generator in that the UPS provides near-instantaneous protection from unanticipated power interruptions from the main power source by providing energy stored in batteries, supercapacitors, or flywheels. The battery duration of a UPS is relatively short but provides sufficient time to start a standby power source, such as a backup generator, or properly shut down the system.

Assessment Objective

an uninterruptible power supply is provided to facilitate [Selection: an orderly shutdown of the system; transition of the system to long-term alternate power] in the event of a primary power source loss.

Assessment Method

Examine

Physical and environmental protection policy procedures addressing emergency power uninterruptible power supply uninterruptible power supply documentation uninterruptible power supply test records system security plan other relevant documents or records

Interview

Organizational personnel with the responsibility for emergency power and/or planning organizational personnel with information security responsibilities

1. Übersicht

Bezeichnung Standard
PE-11(01) Alternate Power Supply — Minimal Operational Capability

Control

Provide an alternate power supply for the system that is activated [Selection: manually; automatically] and that can maintain minimally required operational capability in the event of an extended loss of the primary power source.

Discussion

Provision of an alternate power supply with minimal operating capability can be satisfied by accessing a secondary commercial power supply or other external power supply.

Assessment Objective

  1. an alternate power supply provided for the system is activated [Selection: manually; automatically];
  2. the alternate power supply provided for the system can maintain minimally required operational capability in the event of an extended loss of the primary power source.

Assessment Method

Examine

Physical and environmental protection policy procedures addressing emergency power alternate power supply alternate power supply documentation alternate power supply test records system security plan other relevant documents or records

Interview

Organizational personnel with the responsibility for emergency power and/or planning organizational personnel with information security responsibilities
PE-11(02) Alternate Power Supply — Self-contained

Control

Provide an alternate power supply for the system that is activated [Selection: manually; automatically] and that is:
  1. Self-contained;
  2. Not reliant on external power generation; and
  3. Capable of maintaining [Selection: minimally required operational capability; full operational capability] in the event of an extended loss of the primary power source.

Discussion

The provision of a long-term, self-contained power supply can be satisfied by using one or more generators with sufficient capacity to meet the needs of the organization.

Assessment Objective

an alternate power supply provided for the system is activated [Selection: manually; automatically];
  1. the alternate power supply provided for the system is self-contained;
  2. the alternate power supply provided for the system is not reliant on external power generation;
  3. the alternate power supply provided for the system is capable of maintaining [Selection: minimally required operational capability; full operational capability] in the event of an extended loss of the primary power source.

Assessment Method

Examine

Physical and environmental protection policy procedures addressing emergency power alternate power supply alternate power supply documentation alternate power supply test records system security plan other relevant documents or records

Interview

Organizational personnel with the responsibility for emergency power and/or planning organizational personnel with information security responsibilities