+INF.5.A25 Increased Protection Against Fire and Smoke Damage [Planner] (H)

INF.5.A25 Increased Protection Against Fire and Smoke Damage [Planner] (H)

Room-forming components, as well as doors, windows, and ventilation flaps, SHOULD resist fire and smoke for at least 90 minutes. The supply lines SHOULD guarantee a functional integrity of at least 90 minutes.

In case of very high protection needs, the room envelope SHOULD be designed as a separate fire zone. Fire dampers controlled by smoke detectors SHOULD be installed in ventilation ducts. Cable trays SHOULD be routed through separate fire zones until they enter the room.

In case of very high protection needs, an early fire detection system and an automatic extinguishing system SHOULD be provided. Fire and smoke detectors SHOULD be connected to the fire alarm control panel. The early fire detection system and the automatic extinguishing system SHOULD be connected to the two-line power supply with UPS and EPS.