+INF.12.A17 Redundancies for IT Cabling [IT Operation Department] (H)

INF.12.A17 Redundancies for IT Cabling [IT Operation Department] (H)

Consideration SHOULD be given to creating redundant primary IT cabling that is routed through independent trays. Whether or not redundant connections to IT or telecommunication providers should be installed SHOULD also be examined. In case of high or very high availability requirements, consideration SHOULD be given to installing redundant secondary and tertiary cabling in the relevant buildings. Redundantly designed parts of the secondary cabling SHOULD be routed through different fire zones. If redundant cabling is used, its proper functioning SHOULD be checked at regular intervals.