+INF.14.A3 Secure Connection of Building Services and Building Services Systems (B)

INF.14.A3 Secure Connection of Building Services and Building Services Systems (B)

For all building services systems, BACS, and BACS-relevant components, it MUST be specified whether actions may be triggered by other building services systems, BACS, and BACS-relevant components. If this type of integration is allowed, rules SHOULD be set regarding which automated actions may be triggered by which information from a BACS.

If a building services system is to be coupled with a BACS but cannot or must not be integrated into the BACS, the building services system information to be reported to the BACS MUST be defined.

Both the integration of building services systems into a BACS and the non-reactive coupling of building systems to BACS MUST be adequately secured. The connections between building services systems MUST also be adequately secured.

In particular, the sequence and function chains within or between BACS MUST be adequately planned for this purpose. All transitions between trades and technologies MUST be taken into account.

These process and function chains MUST be comprehensively tested and readjusted in the event of any malfunction.

The specifications MUST be fully documented. The documentation SHOULD be checked both regularly and whenever necessary to ensure that it is still up to date. In case of deviations, the cause MUST be identified and corrected.