+INF.14.A5 Documentation of BACS (B)
|
INF.14.A5 Documentation of BACS (B)
The many different components and points of access pertaining to BACS MUST be documented. This documentation MUST be checked and adapted both regularly and in case of changes within the BACS in question. In particular, all deactivated physical communication interfaces, protocols, and points of access to the BACS MUST be documented. Furthermore, all interactions and dependencies of BACS-relevant components, as well as of building services systems integrated into or coupled with BACS, MUST be documented. The available and utilised security features of the protocols in use SHOULD be documented. The documentation SHOULD be coordinated for all BACS with regard to their content and data structures.
1. Übersicht
1.1 Referenzen
1.2 Identifizierte Anforderungen
1.3 Zugehörige Regulierungen
2. Identifizierte Anforderungen
Anforderungen