+PS-01.02AC

1. Übersicht

PS-01.02AC

The security requirements include time limits in order to provide self-sufficient operation of a location for at least 72 hours in the event of a failure of the external power supply, or until all services are transferred to another location.

Incorrect planning can endanger the operational safety and availability of the premises or buildings. This can result from an incorrect assessment of elementary hazards at the site (e.g. air traffic, earthquakes, floods, hazardous substances) as well as an incorrect conception of the bandwidth or energy supply.

Premises and buildings related to the cloud service provided include data centres and server rooms housing system components used to process cloud service customer data (including data centres for backup or redundancy purposes) and the technical utilities required to operate these system components (e.g. power supply, refrigeration, fire-fighting, telecommunications, security, etc.).

Premises and buildings in which no data from cloud service customers is processed or stored (e.g. offices of the cloud service provider, server rooms with system components for internal development and test systems) adhere to requirements specifically covered under PS-08.

The 72-hour time frame for self-sufficient operation aligns with guidelines for government agencies, businesses and critical infrastructure operators (KRITIS) as per the Federal Office for Civil Protection and Disaster Assistance (BBK).