+PS-03.04B
|
PS-03.04B
The surrounding wall constructions as well as the locking mechanisms meet the associated requirements. Supplementary information The resistance class RC4 according to DIN EN 1627 stipulates that doors, windows and other components shall withstand a break-in attempt for at least ten minutes. The US standard SD-STD-01.01 Rev.G. is an international equivalent to this standard. However, fulfilling the objective of this criteria does not necessarily imply that those standards have to be fulfilled. Additionally, the subcriterion demands that all construction elements as a whole lead to a resistance time to break-in attempts for at least ten minutes. Consequently, it does not necessarly demand that all individual construction elements have to fulfil this requirement on their own, provided the combined measures effectively delay an external attack for the required time.
1. Επισκόπηση
1.1 Παραπομπές
1.2 Εντοπισμένες απαιτήσεις
1.3 Σχετικοί κανονισμοί
2. Εντοπισμένες απαιτήσεις
3. Σχετικοί κανονισμοί
Κανονισμοί
| Πηγή |
Κανονισμός |
Συνδεδεμένα ζητήματα
- BSI -
EN: Publications of the Bundesamt für Sicherheit in der Informationstechnik (BSI, Federal Office for Information Security), https://www.bsi.bund.de/. This is not an official BSI website. Only the versions published by the BSI are authoritative.
DE: Veröffentlichungen des Bundesamts für Sicherheit in der Informationstechnik (BSI), https://www.bsi.bund.de/. Kein amtlicher Auftritt des BSI. Maßgeblich sind allein die vom BSI veröffentlichten Fassungen.
|