+IND.2.1 General ICS Components
---+IND.2.1.G1. Insecure System Configuration
---+IND.2.1.G2. Insufficient User and Authorisation Management
---+IND.2.1.G3. Insufficient Logging
---+IND.2.1.G4. Manipulation and Sabotage of an ICS Component
---+IND.2.1.G5. Use of Insecure Protocols
---+IND.2.1.G6. Denial-of-Service (DoS) Attacks
---+IND.2.1.G7. Malware
---+IND.2.1.G8. Interception of Information/Espionage
---+IND.2.1.G9. Manipulated Firmware
---+IND.2.1.A1 Restriction of Access to Configuration and Maintenance Interfaces [OT Operations] (B)
---+IND.2.1.A2 Using Secure Transmission Protocols for Configuration and Maintenance [Maintenance Personnel, OT Operations] (B)
---+IND.2.1.A4 Disabling or Uninstalling Unused Services, Functions, and Interfaces [Maintenance Personnel, OT Operations] (B)
---+IND.2.1.A6 Network Segmentation [OT Operations, Planner] (B)
---+IND.2.1.A7 Creating Backups [OT Operations] (S)
---+IND.2.1.A8 Protection Against Malware [OT Operations] (S)
---+IND.2.1.A11 Maintenance of ICS Components [Employee, OT Operations, Maintenance Personnel] (S)
---+IND.2.1.A13 Appropriate Commissioning of ICS Components [OT Operations] (S)
---+IND.2.1.A16 Protecting External Interfaces [OT Operations] (S)
---+IND.2.1.A17 Use of Secure Protocols for the Transmission of Measurement and Control Data [OT Operations] (S)
---+IND.2.1.A18 Communication in the Event of Incidents [OT Operations, Employee] (S)
---+IND.2.1.A19 Security Tests [OT Operations] (H)
---+IND.2.1.A20 Trustworthy Code [OT Operations] (H)

IND.2.1 General ICS Components

Introduction

An ICS component is an electronic component that controls or regulates a machine or system. It is thus part of an industrial control system (ICS) or, in more general terms, operational technology (OT). These components may include programmable logic controllers (PLC), sensors, actuators, a machine, or other parts of an ICS.

Due to the typically high availability requirements in OT environments and the often extreme environmental conditions (such as heat, cold, dust, vibration, or corrosion), ICS components have always been designed to be robust devices with high reliability and long service life.

ICS components are normally configured and programmed using special software from the respective manufacturer. This is performed either using programming devices (e.g. as an application under Windows or Linux) or via an engineering station that loads application programs into the programmable logic controllers.

The Information Security Officer role may have different names in the field of industrial automation depending on the type and orientation of the organisation in question. These alternative names include "ICS Information Security Officer (ICS-ISO)" and "Industrial Security Officer".

Objective

The objective of this module is to secure all kinds of ICS components regardless of their manufacturer, type, purpose, and application site. The module may be used for an individual device or for a modular device consisting of several components.

Scoping and Modelling

Module IND.2.1 General ICS Components must be applied to each ICS component used in the information domain under consideration.

The requirements have been drawn up for a generic ICS component. Additional modules are available for specific ICS components such as sensors and actuators or machines; see, for example, IND.2.3 Sensors and Actuators or IND.2.4 Machine. These describe requirements that go beyond the general requirements of this module and must be met additionally.

This module does not contain organisational requirements for safeguarding an ICS component. The requirements of module IND.1 Process Control and Automation Technology must be implemented for this purpose.

Useful Resources

In the “ICS Security Compendium”, the Federal Office for Information Security (BSI) provides assistance for manufacturers and integrators of ICS in terms of testing components and IT security safeguards in ICS.

The German Association of Energy and Water Industries (BDEW) and Oesterreichs E-Wirtschaft offer assistance on the secure operation of control and telecommunication systems in the white paper “Requirements for Secure Control and Telecommunication Systems”.

NIST Special Publication 800-82, “Guide to Industrial Control Systems (ICS) Security”, describes how IT security can be implemented for industrial control systems.

1. Επισκόπηση

Τίτλος Πρότυπο
IND.2.1.A1 Restriction of Access to Configuration and Maintenance Interfaces [OT Operations] (B)

Passwords set by default or by the manufacturer MUST be changed (see ORP.4 Identity and Access Management). These changes MUST be documented. Passwords MUST be stored securely.

It MUST be ensured that only authorised employees are allowed to access the configuration and maintenance interfaces of ICS components. The configuration of an ICS component MUST ONLY be changed after the approval or authentication of the person in charge.

IND.2.1.A2 Using Secure Transmission Protocols for Configuration and Maintenance [Maintenance Personnel, OT Operations] (B)

Secure protocols MUST be implemented for configuring and maintaining ICS components. Information MUST be protected during transmission.

IND.2.1.A4 Disabling or Uninstalling Unused Services, Functions, and Interfaces [Maintenance Personnel, OT Operations] (B)

All services, features, and interfaces of ICS components that are not being used MUST be disabled or uninstalled.

IND.2.1.A6 Network Segmentation [OT Operations, Planner] (B)

ICS components MUST be separated from office IT. If ICS components depend on other components in the network in question, this SHOULD be documented sufficiently. ICS components SHOULD communicate as little as possible with other ICS components.

IND.2.1.A7 Creating Backups [OT Operations] (S)

Backups MUST be created prior to each system change in an ICS component.

IND.2.1.A8 Protection Against Malware [OT Operations] (S)

ICS components SHOULD be protected against malware by suitable mechanisms (see OPS.1.1.4 Protection Against Malware). If an anti-virus protection program is used in this regard, the program and the virus signatures approved by the manufacturer SHOULD always be up to date.

If the resources on the ICS component are not sufficient or real-time requests could be endangered by the use of anti-virus protection programs, alternative safeguards (such as the isolation of the ICS component or the production network) SHOULD be implemented.

IND.2.1.A11 Maintenance of ICS Components [Employee, OT Operations, Maintenance Personnel] (S)

The latest approved security updates SHOULD always be installed when maintaining an ICS component. Updates for the respective operating system SHOULD only be installed following approval by the manufacturer of a given ICS component. Alternatively, updates SHOULD be checked in a test environment before they are used in a productive ICS component. Maintenance SHOULD be performed on short notice for critical security updates.

IND.2.1.A13 Appropriate Commissioning of ICS Components [OT Operations] (S)

Before they are commissioned, ICS components SHOULD correspond to the latest internally approved firmware, software, and patch status.

New ICS components SHOULD be integrated into existing operating, monitoring, and information security management processes.

IND.2.1.A16 Protecting External Interfaces [OT Operations] (S)

Externally accessible interfaces SHOULD be protected against misuse.

IND.2.1.A17 Use of Secure Protocols for the Transmission of Measurement and Control Data [OT Operations] (S)

Measurement or control data SHOULD be protected against unauthorised access or changes during transmission. Whether this is necessary or feasible SHOULD be checked in situations involving applications with real-time requirements. If measurement or control data is transmitted using public networks, it SHOULD be protected appropriately.

IND.2.1.A18 Communication in the Event of Incidents [OT Operations, Employee] (S)

There SHOULD be alternative and independent communication options that an organisation can use to maintain its ability to function in the event of malfunctions.

IND.2.1.A19 Security Tests [OT Operations] (H)

Regular security tests SHOULD be carried out to check whether the technical security safeguards in place are still implemented efficiently. The security tests SHOULD NOT be carried out while the system is running. Such tests SHOULD be scheduled for maintenance periods. The results SHOULD be documented. Identified risks SHOULD be evaluated and addressed.

IND.2.1.A20 Trustworthy Code [OT Operations] (H)

Firmware updates or new control programs SHOULD ONLY be installed after their integrity has been checked. They SHOULD only come from trusted sources.