+INF.2.A29 Avoidance and Monitoring of Unnecessary Wiring [Building Services, Planner] (B)

INF.2.A29 Avoidance and Monitoring of Unnecessary Wiring [Building Services, Planner] (B)

The cables laid in a data centre MUST be restricted to those that directly supply the technology installed there (usually IT and, if applicable, cooling technology). If structural reasons make it unavoidable to run lines through a data centre in order to supply areas other than those within the data centre, this MUST be documented along with suitable justification. The risks posed by such lines MUST be minimised by appropriate safeguards (e.g. enclosures and monitoring).

The aforementioned lines may be routed through server rooms without justifying why this is unavoidable, but they MUST be treated in the same way as described for data centres.

Messages from systems that monitor such lines MUST be checked and evaluated immediately to determine whether a threat is present. Countermeasures MUST be implemented in a timely manner according to the threat level identified (see also INF.2.A13 Planning and Installation of Alarm Systems).