+INF.14.A24 Time Synchronisation for BACS (S)
|
INF.14.A24 Time Synchronisation for BACS (S)
All components and building services systems connected in BACS SHOULD use a synchronous time to ensure automated measurement, control, and regulation (see also OPS.1.2.6 NTP Time Synchronisation). BACS that are interconnected SHOULD also use a synchronous time. If BACS span multiple building complexes or properties, time synchronisation SHOULD be ensured for all these buildings. If real-time communication is required within a BACS, PTP or a comparable mechanism SHOULD be used for time synchronisation instead of NTP.