+INF.5.A19 Redundancy of the Technical Infrastructure Room [Planner] (H)
|
INF.5.A19 Redundancy of the Technical Infrastructure Room [Planner] (H)
A technical infrastructure room SHOULD be designed redundantly. Both rooms SHOULD have a dedicated electrical sub-distribution that is directly supplied by the low-voltage main distribution panel (LVMDP). Both rooms SHOULD be assigned to different fire zones and, if necessary, have their own respective ventilation and air-conditioning systems.