+PS-03.03B

PS-03.03B

The outer doors, windows and other construction elements exhibit an appropriate security level so that their combined resistance time withstand a break-in attempt for at least ten minutes in total. This time period applies from the moment an external intruder is detected (e.g. by perimeter surveillance).

Supplementary information

The resistance class RC4 according to DIN EN 1627 stipulates that doors, windows and other components shall withstand a break-in attempt for at least ten minutes. The US standard SD-STD-01.01 Rev.G. is an international equivalent to this standard. However, fulfilling the objective of this criteria does not necessarily imply that those standards have to be fulfilled.

Additionally, the subcriterion demands that all construction elements as a whole lead to a resistance time to break-in attempts for at least ten minutes. Consequently, it does not necessarly demand that all individual construction elements have to fulfil this requirement on their own, provided the combined measures effectively delay an external attack for the required time.

1. Panoramica

Titolo Standard

1.1 Riferimenti

1.2 Requisiti identificati

1.3 Regolamentazioni correlate

2. Requisiti identificati

Requisiti
Fonte Requisito

3. Regolamentazioni correlate

Regolamentazioni
Fonte Regolamentazione

Ticket collegati

Collegamenti
Tipo di collegamento Ticket
is blocked by Physical Security of Offices, Rooms & Facilities