+Article 13 9.

Article 13 9.

The putting into operation of the following electrical switchgear using, or whose functioning relies upon, fluorinated greenhouse gases in insulating or breaking medium shall be prohibited as follows:

(a) 

from 1 January 2026, medium voltage electrical switchgear for primary and secondary distribution up to and including 24 kV;

(b) 

from 1 January 2030, medium voltage electrical switchgear for primary and secondary distribution from more than 24 kV up to and including 52 kV;

▼C1

(c) 

from 1 January 2028, high voltage electrical switchgear from more than 52 kV up to and including 145 kV and up to and including 50 kA short circuit current, with a global warming potential of 1 or more;

▼B

(d) 

from 1 January 2032, high voltage electrical switchgear of more than 145 kV or more than 50 kA short circuit current, with a global warming potential of 1 or more.

1. Apžvalga

,
Pavadinimas Reguliavimas

1.1 Nuorodos

1.2 Nustatyti reikalavimai

1.3 Susiję standartai

2. Nustatyti reikalavimai

Reikalavimai
Šaltinis Reikalavimas

3. Susiję standartai

Standartai
Šaltinis Reikalavimas