+INF.2.A9 Use of an Extinguishing or Fire Prevention System [Building Services] (B)
|
INF.2.A9 Use of an Extinguishing or Fire Prevention System [Building Services] (B)
An extinguishing or fire prevention system in line with the current state of the art MUST be installed in a data centre. If this is not possible, technical (especially a wide-area early detection system; see INF.2.A17 Early Fire Detection) and organisational measures (trained personnel and response plans for early fire detection alarms) MUST ensure that early fire detection alarms are responded to immediately and within no more than three minutes. In server rooms without an extinguishing or fire prevention system, hand-held fire extinguishers with suitable extinguishing agents MUST be available in sufficient number and size. Attention MUST be paid to the fact that these provisions do not affect any additional building code requirements regarding the provision of hand-held fire extinguishers. The fire extinguishers MUST be mounted so that they are easy to access in case of a fire. Each fire extinguisher must be inspected and serviced regularly. All staff who are allowed to enter a data centre or server room MUST be instructed in the use of hand-held fire extinguishers.