+INF.5.A13 Protection Against Fire and Smoke Damage [Planner, Building Services] (S)

INF.5.A13 Protection Against Fire and Smoke Damage [Planner, Building Services] (S)

Irrespective of the building regulations pertaining to fire protection requirements that apply to a technical infrastructure room, all room-forming components, as well as doors and windows, SHOULD be equally smoke-tight. They SHOULD resist fire and smoke for at least 30 minutes. Fire loads in the vicinity of cable trays SHOULD be avoided.