+INF.5.A15 Lightning and Overvoltage Protection [Planner, Building Services] (S)

INF.5.A15 Lightning and Overvoltage Protection [Planner, Building Services] (S)

A lightning and overvoltage protection concept should be developed and implemented in accordance with the principle of energetic coordination (see DIN EN 62305). A technical infrastructure room SHOULD be classified in accordance with lightning protection zone 2 (LPZ 2) at minimum. The lightning and overvoltage protection devices SHOULD be checked regularly to ensure they are fit for purpose and replaced if necessary.

1. Übersicht

Bezeichnung Standard

1.1 Referenzen

1.2 Identifizierte Anforderungen

1.3 Zugehörige Regulierungen

2. Identifizierte Anforderungen

Anforderungen
Quelle Anforderung

3. Zugehörige Regulierungen

Regulierungen
Quelle Regulierung

Verknüpfte Vorgänge