+INF.5.A15 Lightning and Overvoltage Protection [Planner, Building Services] (S)

INF.5.A15 Lightning and Overvoltage Protection [Planner, Building Services] (S)

A lightning and overvoltage protection concept should be developed and implemented in accordance with the principle of energetic coordination (see DIN EN 62305). A technical infrastructure room SHOULD be classified in accordance with lightning protection zone 2 (LPZ 2) at minimum. The lightning and overvoltage protection devices SHOULD be checked regularly to ensure they are fit for purpose and replaced if necessary.