+INF.5.A22 Redundant Power Supply Design [Planner] (H)
|
INF.5.A22 Redundant Power Supply Design [Planner] (H)
In a technical infrastructure room, there SHOULD be a two-line power supply that runs all the way from the low-voltage main distribution board (LVMDS) to the consumer. These power supplies SHOULD be located in separate fire zones. The LVMDS SHOULD be redundant in operation.
1. Panoramica
1.1 Riferimenti
1.2 Requisiti identificati
1.3 Regolamentazioni correlate
2. Requisiti identificati
Requisiti
| Fonte |
Requisito |
3. Regolamentazioni correlate
Regolamentazioni
| Fonte |
Regolamentazione |
Ticket collegati
|