+INF.5.A22 Redundant Power Supply Design [Planner] (H)
|
INF.5.A22 Redundant Power Supply Design [Planner] (H)
In a technical infrastructure room, there SHOULD be a two-line power supply that runs all the way from the low-voltage main distribution board (LVMDS) to the consumer. These power supplies SHOULD be located in separate fire zones. The LVMDS SHOULD be redundant in operation.