+INF.2.A23 Appropriate Design of Data Centre Cabling [Building Services] (H)

INF.2.A23 Appropriate Design of Data Centre Cabling [Building Services] (H)

Cable routes in data centres SHOULD be carefully planned and implemented. Cable trays in data centres SHOULD be carefully designed in terms of their arrangement and dimensioning so that separation of voltage levels and a sensible distribution of cables on the trays is possible, and that sufficient space is also available for future increases in demand. To ensure the optimal supply of IT hardware that has two power supply units, a two-line A-B supply SHOULD be set up from the low-voltage main distributor for the IT operating areas in question. Pairs of redundant lines SHOULD be laid in separate trays.

1. Apžvalga

Pavadinimas Standartas

1.1 Nuorodos

1.2 Nustatyti reikalavimai

1.3 Susiję teisės aktai

2. Nustatyti reikalavimai

Reikalavimai
Šaltinis Reikalavimas

3. Susiję teisės aktai

Teisės aktai
Šaltinis Reguliavimas

Susietos užduotys