+INF.2.A17 Use of Early Fire Detection [Planner, Building Services] (B)
|
INF.2.A17 Use of Early Fire Detection [Planner, Building Services] (B)
A data centre MUST be equipped with an early fire detection system. A server room SHOULD be equipped with an early fire detection system. Early fire detection alarms MUST be routed to a continuously staffed department that can initiate a corresponding check and a protective response within three minutes. Alternatively, an automatic protective response MUST be initiated. In order to achieve a balance between fire protection and availability, it MUST be ensured that equipment providing redundancy is not located together within the effective range of the same voltage isolation circuit.
1. Ħarsa ġenerali
1.1 Referenzi
1.2 Rekwiżiti identifikati
1.3 Regolamenti relatati
2. Rekwiżiti identifikati
3. Regolamenti relatati
Regolamenti
| Sors |
Regolamentazzjoni |
Kwistjonijiet marbuta
|