+INF.2.A17 Use of Early Fire Detection [Planner, Building Services] (B)

INF.2.A17 Use of Early Fire Detection [Planner, Building Services] (B)

A data centre MUST be equipped with an early fire detection system. A server room SHOULD be equipped with an early fire detection system. Early fire detection alarms MUST be routed to a continuously staffed department that can initiate a corresponding check and a protective response within three minutes. Alternatively, an automatic protective response MUST be initiated. In order to achieve a balance between fire protection and availability, it MUST be ensured that equipment providing redundancy is not located together within the effective range of the same voltage isolation circuit.