+INF.2.A15 Overvoltage Protection Devices [Planner, Building Services] (S)

INF.2.A15 Overvoltage Protection Devices [Planner, Building Services] (S)

A lightning and overvoltage protection concept SHOULD be drawn up on the basis of the currently valid standard (DIN EN 62305 parts 1 to 4). The lightning protection zones (LPZ) required for the proper operation of a data centre must be defined. For all the facilities required for the proper operation of a data centre and its ability to provide services, this SHOULD be at least LPZ 2. All overvoltage protection equipment SHOULD be subject to a comprehensive test once a year in accordance with DIN EN 62305-3 (table E.2).

1. Visão geral

Título Norma

1.1 Referências

1.2 Requisitos identificados

1.3 Regulamentos relacionados

2. Requisitos identificados

Requisitos
Fonte Requisito

3. Regulamentos relacionados

Regulamentos
Fonte Regulamentação

Pedidos ligados

Ligações
Tipo de ligação Pedido
blocks G 0.1 Fire
blocks G 0.25 Failure of Devices or Systems