+Article 21 3

Article 21 3

3.   Operators of refrigeration and air conditioning equipment or heat pumps, or fire protection systems, including their circuits, which contain ozone-depleting substances listed in Annex I shall ensure that stationary equipment or systems:

(a)

with a fluid charge of 3 kg or more but less than 30 kg of ozone-depleting substances listed in Annex I are checked for leaks at least once every 12 months, with the exception of equipment with hermetically sealed systems which are labelled as such and contain less than 6 kg of ozone-depleting substances listed in Annex I;

(b)

with a fluid charge of 30 kg or more but less than 300 kg of ozone-depleting substances listed in Annex I are checked for leaks at least once every 6 months;

(c)

with a fluid charge of 300 kg or more of ozone-depleting substances listed in Annex I are checked for leaks at least once every 3 months.

1. Visão geral

,
Título Regulamentação

1.1 Referências

1.2 Requisitos identificados

1.3 Normas relacionadas

2. Requisitos identificados

Requisitos
Fonte Requisito

3. Normas relacionadas

Normas
Fonte Requisito