+ANEXO V USOS CRÍTICOS DE LOS HALONES A QUE SE REFIERE EL ARTÍCULO 9, APARTADO 1
---+1. ‘cut-off date’ means the date after which halons shall not be used for fire extinguishers or …
---+2. ‘new equipment’ means equipment for which, by the cut-off date, neither of the following events …
---+3. ‘new facilities’ means facilities for which, by the cut-off date, neither of the following …
---+4. ‘end date’ means the date after which halons shall not be used for the application concerned and …
---+5. ‘inerting’ means preventing the initiation of combustion of a flammable or explosive atmosphere …
---+6. ‘normally occupied space’ means a protected space in which it is necessary for persons to be …
---+7. ‘normally unoccupied space’ means a protected space that is occupied for limited periods only …
|
ANEXO V USOS CRÍTICOS DE LOS HALONES A QUE SE REFIERE EL ARTÍCULO 9, APARTADO 1
ANEXO V
USOS CRÍTICOS DE LOS HALONES A QUE SE REFIERE EL ARTÍCULO 9, APARTADO 1
A efectos del presente anexo, se entenderá por:
|
1)
|
«fecha límite»: la fecha a partir de la cual no se usarán halones para extintores de incendios o sistemas de protección contra incendios en nuevos aparatos e instalaciones para la aplicación de que se trate;
|
|
2)
|
«nuevos aparatos»: los aparatos en relación con los cuales no se haya producido, antes de la fecha límite, ninguna de las siguientes circunstancias:
|
a)
|
firma del contrato de adquisición o de renovación pertinente;
|
|
b)
|
presentación de una solicitud de homologación o certificación de tipo a la oportuna autoridad reguladora; en el caso de las aeronaves, la presentación de una solicitud de certificación de tipo se refiere a la presentación de una solicitud de nueva certificación de tipo de aeronave;
|
|
|
3)
|
«nuevas instalaciones»: las instalaciones en relación con las cuales no se haya producido, antes de la fecha límite, ninguna de las siguientes circunstancias:
|
a)
|
firma del contrato de renovación pertinente;
|
|
b)
|
presentación de una solicitud de autorización urbanística a la oportuna autoridad reguladora;
|
|
|
4)
|
«fecha terminal»: la fecha a partir de la cual no se usarán halones para la aplicación de que se trate y antes de la cual los extintores de incendios o los sistemas de protección contra incendios que contengan halones se retirarán del servicio;
|
|
5)
|
«inertizar»: impedir el comienzo de la combustión en una atmósfera inflamable o explosiva mediante la adición de un agente inhibidor o diluyente;
|
|
6)
|
«zona habitualmente ocupada»: una zona protegida en la que sea necesaria la presencia constante, o prácticamente constante, de personas para el efectivo funcionamiento de los aparatos o instalaciones; en el caso de aplicaciones militares, la condición de ocupación de la zona protegida sería la aplicable en una situación de combate;
|
|
7)
|
«zona habitualmente desocupada»: una zona protegida ocupada únicamente durante períodos limitados, en particular con fines de mantenimiento, en la que no sea necesaria la presencia constante de personas para el efectivo funcionamiento de los aparatos o instalaciones.
|
USOS CRÍTICOS DE LOS HALONES
|
|
Aplicación
|
Fecha límite
(31 de diciembre del año indicado)
|
Fecha de finalización
(31 de diciembre del año indicado)
|
|
Categoría de aparatos o instalaciones
|
Propósito
|
Tipo de extintor
|
Tipo de halón
|
|
1.
|
En vehículos militares terrestres
|
|
|
1.1.
|
Para la protección de los compartimentos de motores
|
|
Sistema fijo
|
1301
1211
2402
|
2010
|
2035
|
|
1.2.
|
Para la protección de las cabinas de la tripulación
|
|
Sistema fijo
|
1301
2402
|
2011
|
2040
|
|
2.
|
En buques militares de superficie
|
|
|
2.1.
|
Para la protección de las salas de máquinas habitualmente ocupadas
|
|
Sistema fijo
|
1301
2402
|
2010
|
2040
|
|
2.2.
|
Para la protección de las salas de motores habitualmente desocupadas
|
|
Sistema fijo
|
1301
1211
2402
|
2010
|
2035
|
|
2.3.
|
Para la protección de las cámaras eléctricas habitualmente desocupadas
|
|
Sistema fijo
|
1301
1211
|
2010
|
2030
|
|
|
|
2.4.
|
Para la protección de los puestos de control
|
|
Sistema fijo
|
1301
|
2010
|
2030
|
|
2.5.
|
Para la protección de las cámaras de bombas de combustible
|
|
Sistema fijo
|
1301
|
2010
|
2030
|
|
2.6.
|
Para la protección de las zonas de almacenamiento de líquidos inflamables
|
|
Sistema fijo
|
1301
1211
2402
|
2010
|
2030
|
|
3.
|
En submarinos militares
|
|
|
3.1.
|
Para la protección de las salas de máquinas
|
|
Sistema fijo
|
1301
|
2010
|
2040
|
|
3.2.
|
Para la protección de los puestos de control
|
|
Sistema fijo
|
1301
|
2010
|
2040
|
|
3.3.
|
Para la protección de las salas de generadores diésel
|
|
Sistema fijo
|
1301
|
2010
|
2040
|
|
3.4.
|
Para la protección de las cabinas eléctricas
|
|
Sistema fijo
|
1301
|
2010
|
2040
|
|
|
|
4.1.
|
Para la protección de las bodegas de carga habitualmente desocupadas
|
|
Sistema fijo
|
1301
1211
2402
|
2024
|
2040
|
|
4.2.
|
Para la protección de las cabinas de pasajeros y de vuelo
|
|
Extintor portátil
|
1211
2402
|
2014
|
2025
|
|
4.3.
|
Para la protección de las góndolas de motor y las unidades auxiliares de potencia
|
|
Sistema fijo
|
1301
1211
2402
|
2014
|
2040
|
|
4.4.
|
Para la inertización de los depósitos de combustible
|
|
Sistema fijo
|
1301
2402
|
2011
|
2040
|
|
4.5.
|
Para la protección de las bodegas de carga seca
|
|
Sistema fijo
|
1301
1211
2402
|
2011
|
2040
|
|
5.
|
En centros terrestres de mando y comunicaciones de importancia vital para la seguridad nacional
|
|
Para la protección de las zonas habitualmente ocupadas
|
Sistema fijo
|
1301
2402
|
2010
|
2025
|
|
1. Resumen
| Título |
Regulación |
|
1. ‘cut-off date’ means the date after which halons shall not be used for fire extinguishers or …
|
|
1.
|
‘cut-off date’ means the date after which halons shall not be used for fire extinguishers or fire protection systems in new equipment and new facilities for the application concerned;
|
|
|
2. ‘new equipment’ means equipment for which, by the cut-off date, neither of the following events …
|
|
2.
|
‘new equipment’ means equipment for which, by the cut-off date, neither of the following events has occurred:
|
(a)
|
signature of the relevant procurement or development contract;
|
|
(b)
|
submission of a request for type approval or type certification to the appropriate regulatory authority; for aircraft, submission of a request for type certification refers to a submission of a request for a new aircraft type certification;
|
|
|
|
3. ‘new facilities’ means facilities for which, by the cut-off date, neither of the following …
|
|
3.
|
‘new facilities’ means facilities for which, by the cut-off date, neither of the following events has occurred:
|
(a)
|
signature of the relevant development contract;
|
|
(b)
|
submission of a request for planning consent to the appropriate regulatory authority;
|
|
|
|
4. ‘end date’ means the date after which halons shall not be used for the application concerned and …
|
|
4.
|
‘end date’ means the date after which halons shall not be used for the application concerned and by which date the fire extinguishers or fire protection systems containing halons shall be decommissioned;
|
|
|
5. ‘inerting’ means preventing the initiation of combustion of a flammable or explosive atmosphere …
|
|
5.
|
‘inerting’ means preventing the initiation of combustion of a flammable or explosive atmosphere by means of the addition of an inhibiting or diluting agent;
|
|
|
6. ‘normally occupied space’ means a protected space in which it is necessary for persons to be …
|
|
6.
|
‘normally occupied space’ means a protected space in which it is necessary for persons to be present most or all of the time in order for the equipment or facility to function effectively; for military applications, the occupancy status of the protected space is applicable during a combat situation;
|
|
|
7. ‘normally unoccupied space’ means a protected space that is occupied for limited periods only …
|
|
7.
|
‘normally unoccupied space’ means a protected space that is occupied for limited periods only, in particular for undertaking maintenance, and where the continual presence of persons is not necessary for the effective functioning of the equipment or facility.
|
CRITICAL USES OF HALONS
|
|
Application
|
Cut-off date
(31 December of the stated year)
|
End date
(31 December of the stated year)
|
|
Category of equipment or facility
|
Purpose
|
Type of extinguisher
|
Type of halon
|
|
1.
|
On military ground vehicles
|
|
|
1.1.
|
For the protection of engine compartments
|
|
Fixed system
|
1301
1211
2402
|
2010
|
2035
|
|
1.2.
|
For the protection of crew compartments
|
|
Fixed system
|
1301
2402
|
2011
|
2040
|
|
2.
|
On military surface ships
|
|
|
2.1.
|
For the protection of normally occupied machinery spaces
|
|
Fixed system
|
1301
2402
|
2010
|
2040
|
|
2.2.
|
For the protection of normally unoccupied engine spaces
|
|
Fixed system
|
1301
1211
2402
|
2010
|
2035
|
|
2.3.
|
For the protection of normally unoccupied electrical compartments
|
|
Fixed system
|
1301
1211
|
2010
|
2030
|
|
|
|
2.4.
|
For the protection of command centres
|
|
Fixed system
|
1301
|
2010
|
2030
|
|
2.5.
|
For the protection of fuel pump rooms
|
|
Fixed system
|
1301
|
2010
|
2030
|
|
2.6.
|
For the protection of flammable liquid storage compartments
|
|
Fixed system
|
1301
1211
2402
|
2010
|
2030
|
|
3.
|
On military submarines
|
|
|
3.1.
|
For the protection of machinery spaces
|
|
Fixed system
|
1301
|
2010
|
2040
|
|
3.2.
|
For the protection of command centres
|
|
Fixed system
|
1301
|
2010
|
2040
|
|
3.3.
|
For the protection of diesel generator spaces
|
|
Fixed system
|
1301
|
2010
|
2040
|
|
3.4.
|
For the protection of electrical compartments
|
|
Fixed system
|
1301
|
2010
|
2040
|
|
|
|
4.1.
|
For the protection of normally unoccupied cargo compartments
|
|
Fixed system
|
1301
1211
2402
|
2024
|
2040
|
|
4.2.
|
For the protection of cabins and crew compartments
|
|
Portable extinguisher
|
1211
2402
|
2014
|
2025
|
|
4.3.
|
For the protection of engine nacelles and auxiliary power units
|
|
Fixed system
|
1301
1211
2402
|
2014
|
2040
|
|
4.4.
|
For the inerting of fuel tanks
|
|
Fixed system
|
1301
2402
|
2011
|
2040
|
|
4.5.
|
For the protection of dry bays
|
|
Fixed system
|
1301
1211
2402
|
2011
|
2040
|
|
5.
|
In land-based command and communications facilities essential to national security
|
|
For the protection of normally occupied spaces
|
Fixed system
|
1301
2402
|
2010
|
2025
|
|
|
,
1.1 Referencias
1.2 Requisitos identificados
1.3 Estándares relacionados
2. Requisitos identificados
Requisitos
| Fuente |
Requisito |
3. Estándares relacionados
Estándares
| Fuente |
Requisito |
- Builddate: 20.02.2024 00:00:00 -Doknr: CELEX:32024R0590
- EULAW -
EN: Legal acts of the European Union from EUR-Lex, https://eur-lex.europa.eu/. © European Union. Re-use is authorised by Decision 2011/833/EU, provided the source is acknowledged; the consolidated texts are licensed under CC BY 4.0 (EUR-Lex legal notice). Divided into sections and converted into the GRCA format, the wording unchanged. Only the legislation published in the Official Journal of the European Union is deemed authentic.
DE: Rechtsakte der Europäischen Union aus EUR-Lex, https://eur-lex.europa.eu/. © Europäische Union. Weiterverwendung nach Beschluss 2011/833/EU mit Quellenangabe gestattet; die konsolidierten Fassungen stehen unter CC BY 4.0 (Rechtlicher Hinweis von EUR-Lex). In Abschnitte aufgeteilt und in das GRCA-Format umgewandelt, der Wortlaut unverändert. Verbindlich sind allein die im Amtsblatt der Europäischen Union veröffentlichten Rechtsakte.
|