+ALLEGATO II MONITORAGGIO
---+1. Monitoring programmes established pursuant to Article 13(2) for water intended for human …
---+2. Monitoring programmes established pursuant to Article 13(2) shall include one or a combination …
---+3. Monitoring programmes shall also include an operational monitoring programme that provides rapid …
---+4. Member States shall ensure that monitoring programmes are reviewed on a continuous basis and …
---+1. List of parameters Group A The following parameters (Group A) shall be monitored in accordance …
---+2. Sampling frequencies Table 1. Minimum frequency of sampling and analysis for compliance …
---+1. Based on the outcome of the risk assessment of the supply system as referred to in Article 9 …
---+2. As a result of a risk assessment of the supply system, the list of parameters considered in the …
---+1. Sampling points shall be determined so as to ensure compliance with Article 6(1). In the case of …
---+2. Sampling at the point of compliance shall meet the following requirements: (a) compliance …
---+3. Samples for Legionella in domestic distribution systems shall be taken at risk points for …
---+4. Sampling in the distribution network, with the exception of sampling at the consumers’ tap …
|
ALLEGATO II MONITORAGGIO
ALLEGATO II
MONITORAGGIO
Parte A
Obiettivi generali e programmi di monitoraggio per le acque destinate al consumo umano
1. I programmi di monitoraggio stabiliti a norma dell’articolo 13, paragrafo 2, per le acque destinate al consumo umano:
a)
verificano che le misure previste per contenere i rischi per la salute umana in tutta la catena di approvvigionamento (dall’estrazione, al trattamento e allo stoccaggio fino alla distribuzione) siano efficaci e che le acque destinate al consumo umano siano salubri e pulite nel punto in cui i valori devono essere rispettati;
b)
mettono a disposizione informazioni sulla qualità dell’acqua fornita per il consumo umano al fine di dimostrare che gli obblighi di cui all’articolo 4, nonché i valori parametrici stabiliti conformemente all’articolo 5, siano stati rispettati;
c)
individuare le misure più adeguate per mitigare i rischi per la salute umana.
2. I programmi di monitoraggio stabiliti a norma dell’articolo 13, paragrafo 2, includono una delle due seguenti misure o una loro combinazione:
a)
raccolta e analisi di campioni discreti delle acque;
b)
misurazioni registrate attraverso un processo di monitoraggio continuo.
Inoltre, i programmi di monitoraggio possono consistere in:
a)
ispezioni delle registrazioni inerenti la funzionalità e lo stato di manutenzione delle attrezzature;
b)
ispezioni dell’area di estrazione delle acque, e del trattamento, dello stoccaggio e delle infrastrutture di distribuzione fatte salve le prescrizioni in materia di monitoraggio di cui all’articolo 8, paragrafo 2, primo comma, lettera c), e all’articolo 10, paragrafo 1, primo comma, lettera b).
3. I programmi di monitoraggio comprendono anche un programma di monitoraggio operativo, che fornisce una rapida panoramica delle prestazioni operative e dei problemi relativi alla qualità dell’acqua, e che consente di adottare rapidamente provvedimenti correttivi predeterminati. Tali programmi operativi riguardano specificamente l’erogazione, tenendo conto dei risultati dell’individuazione dei pericoli e degli eventi pericolosi e della valutazione del rischio del sistema di fornitura, e sono intesi a confermare l’efficacia di tutte le misure di controllo su estrazione, trattamento, distribuzione e stoccaggio.
Il programma di monitoraggio operativo include il monitoraggio del parametro della «torbidità presso l’impianto di fornitura dell’acqua» per controllare periodicamente l’efficacia dei processi di eliminazione fisica mediante filtrazione, in conformità con i valori di riferimento e le frequenze indicate nella tabella seguente (non applicabile alle acque sotterranee in cui la torbidità è causata dal ferro e dal manganese):
|
Parametro operativo
|
Valore di riferimento
|
|
Torbidità presso l’impianto di fornitura dell’acqua
|
0,3 NTU nel 95 % dei campioni e nessun superamento di 1 NTU
|
|
Volume (m3) di acqua distribuito o prodotto ogni giorno in una zona di approvvigionamento
|
Frequenza minima di campionamento e analisi
|
|
≤ 1 000
|
Settimanale
|
|
> 1 000 fino a ≤ 10 000
|
Una volta al giorno
|
|
> 10 000
|
Continuo
|
Il programma di monitoraggio operativo include inoltre il monitoraggio dei seguenti parametri nelle acque non trattate al fine di controllare l’efficacia dei processi di trattamento contro i rischi microbiologici:
|
Parametro operativo
|
Valore di riferimento
|
Unità di misura
|
Note
|
|
Colifagi somatici
|
50 (per acque non trattate)
|
unità formanti placca (PFU)/100 ml
|
Questo parametro deve essere misurato se indicato come appropriato dalla valutazione del rischio. Se rilevato in acque non trattate in concentrazioni > 50 PFU/100 ml, dovrebbe essere analizzato dopo fasi del processo di trattamento volte a determinare la riduzione logaritmica da parte delle barriere esistenti e valutare se il rischio di resistenza di virus patogeni è sufficientemente sotto controllo.
|
4. Gli Stati membri provvedono affinché i programmi di monitoraggio siano riesaminati regolarmente e aggiornati o confermati almeno ogni sei anni.
Parte B
Parametri e frequenze di campionamento
Gruppo A
Occorre monitorare i seguenti parametri (gruppo A) secondo la frequenza di cui alla tabella 1 del punto 2:
a)
Escherichia coli (E. coli), enterococchi intestinali, batteri coliformi, conteggio delle colonie a 22 °C, colore, torbidità, sapore, odore, pH, e conduttività;
b)
altri parametri ritenuti pertinenti per il programma di monitoraggio, conformemente all’articolo 5, paragrafo 3, e, se del caso, attraverso la valutazione del rischio del sistema di fornitura a norma dell’articolo 9 e alla parte C del presente allegato.
In circostanze specifiche, ai parametri del gruppo A vanno aggiunti quelli elencati di seguito:
a)
ammonio e nitrito, se si utilizza la cloramina;
b)
alluminio e ferro, se utilizzati come prodotti chimici per il trattamento delle acque.
Escherichia coli (E. coli) ed enterococchi intestinali sono considerati «parametri fondamentali» e le loro frequenze di monitoraggio non possono essere oggetto di una riduzione dovuta a una valutazione del rischio della fornitura conformemente all’articolo 9 e alla parte C del presente allegato. Essi sono sempre monitorati almeno con la frequenza indicata nella tabella 1 del punto 2.
Gruppo B
Al fine di determinare la conformità con tutti i valori parametrici stabiliti alla presente direttiva, occorre monitorare tutti gli altri parametri non previsti nel gruppo A e stabiliti a norma dell’articolo 5, eccetto i parametri dell’allegato I, parte D, alla frequenza indicata nella tabella 1 del punto 2, tranne qualora una diversa frequenza di campionamento sia determinata sulla base della valutazione del rischio della fornitura effettuata conformemente all’articolo 9 e alla parte C del presente allegato.
2. Frequenza di campionamento
Tabella 1 Frequenza minima di campionamento e analisi per il monitoraggio di conformità
|
Volume di acqua distribuito o prodotto ogni giorno in una zona di approvvigionamento
(cfr. note 1 e 2) m3
|
Parametri — gruppo A
numero di campioni all’anno
|
Parametri — gruppo B
numero di campioni all’anno
|
|
|
< 10
|
> 0 (cfr. nota 4)
|
> 0 (cfr. nota 4)
|
|
≥ 10
|
≤ 100
|
2
|
1 (cfr. nota 5)
|
|
> 100
|
≤ 1 000
|
4
|
1
|
|
> 1 000
|
≤ 10 000
|
4 per i primi 1 000 m3/d
+ 3 per ogni 1 000 m3/d aggiuntivi e relativa frazione del volume totale
(cfr. nota 3)
|
1 per i primi 1 000 m3/d
+ 1 per ogni 4 500 m3/d aggiuntivi e relativa frazione del volume totale
(cfr. nota 3)
|
|
> 10 000
|
≤ 100 000
|
3 per i primi 10 000 m3/d
+ 1 per ogni 10 000 m3/d aggiuntivi e relativa frazione del volume totale
(cfr. nota 3)
|
|
> 100 000
|
|
12 per i primi 100 000 m3/d
+ 1 per ogni 25 000 m3/d aggiuntivi e relativa frazione del volume totale
(cfr. nota 3)
|
|
Nota 1: una zona di approvvigionamento è una zona geograficamente definita all’interno della quale le acque destinate al consumo umano provengono da una o varie fonti e dentro la quale la qualità dell’acqua può essere considerata sostanzialmente uniforme.
Nota 2: i volumi calcolati rappresentano una media su un anno civile. Per determinare la frequenza minima è possibile basarsi sul numero di abitanti in una zona di approvvigionamento invece che sul volume d’acqua, supponendo un consumo di 200 l/(giorno*pro capite).
Nota 3: la frequenza indicata è così calcolata: ad esempio 4 300 m3/d = 16 campioni per i parametri del gruppo A (quattro per i primi 1 000 m3/d + 12 per gli ulteriori 3 300 m3/d).
Nota 4: per i fornitori di acqua, se non è stata concessa un’esenzione a norma dell’articolo 3, paragrafo 3, lettera b), gli Stati membri fissano la frequenza minima di campionamento per i parametri del gruppo A e del gruppo B, a condizione che i parametri fondamentali siano monitorati almeno una volta all’anno.
Nota 5: gli Stati membri possono ridurre la frequenza di campionamento, a condizione che tutti i parametri fissati conformemente all’articolo 5 siano monitorati almeno una volta ogni sei anni come pure siano monitorati nei casi in cui una nuova fonte di acqua sia integrata nel sistema di fornitura d’acqua o siano realizzate modifiche a tale sistema, per cui si possano prevedere effetti potenzialmente negativi sulla qualità dell’acqua.
|
Parte C
Valutazione e gestione del rischio del sistema di fornitura
1. Sulla base dei risultati della valutazione del rischio del sistema di fornitura di cui all’articolo 9, viene ampliato l’elenco dei parametri considerati nel monitoraggio e vengono aumentate le frequenze di campionamento stabilite nella parte B, se si verifica una qualsiasi delle seguenti condizioni:
a)
l’elenco dei parametri o delle frequenze di cui al presente allegato non è sufficiente a soddisfare gli obblighi imposti a norma dell’articolo 13, paragrafo 1;
b)
è necessario procedere a ulteriori monitoraggi ai fini dell’articolo 13, paragrafo 5;
c)
è necessario fornire le garanzie di cui al punto 1, lettera a), della parte A;
d)
è necessario aumentare la frequenza di campionamento conformemente all’articolo 8, paragrafo 4, primo comma, lettera a).
2. A seguito della valutazione del rischio del sistema di fornitura, possono essere ridotti l’elenco dei parametri considerati nel monitoraggio e le frequenze di campionamento stabilite nella parte B, a condizione che si osservino tutte le seguenti condizioni:
a)
l’ubicazione e la frequenza del campionamento è determinata in relazione all’origine del parametro, nonché alla variabilità e alla tendenza a lungo termine riguardante la sua concentrazione, tenendo conto dell’articolo 6;
b)
per quanto riguarda la riduzione della frequenza di campionamento minima di un parametro, i risultati ottenuti da campioni raccolti ad intervalli regolari nell’arco di un periodo di almeno tre anni a partire da punti di campionamento rappresentativi dell’intera zona di approvvigionamento sono tutti inferiori al 60 % del valore di parametro;
c)
per quanto riguarda la rimozione di un parametro dall’elenco di quelli da sottoporre a monitoraggio, i risultati ottenuti dai campioni raccolti ad intervalli regolari nell’arco di un periodo di almeno tre anni a partire da punti di campionamento rappresentativi dell’intera zona di approvvigionamento sono tutti inferiori al 30 % del valore di parametro;
d)
per quanto riguarda la rimozione di un parametro dall’elenco di parametri da sottoporre a monitoraggio, la decisione è basata sui risultati della valutazione del rischio, che tiene conto dei risultati del controllo delle fonti di acqua destinata al consumo umano e deve confermare che la salute umana sia protetta dagli effetti nocivi di eventuali contaminazioni delle acque destinate al consumo umano, come stabilito all’articolo 1;
e)
per quanto riguarda la riduzione della frequenza di campionamento di un parametro oppure rimuovere un parametro dall’elenco dei parametri da controllare, la valutazione del rischio conferma che nessun elemento ragionevolmente prevedibile possa provocare un deterioramento della qualità delle acque destinate al consumo umano.
I risultati del controllo, comprovanti il rispetto delle condizioni di cui ai punti da 2), lettera b) a 2), lettera e), che siano già disponibili entro il 12 gennaio 2021, possono essere utilizzati a decorrere da tale data al fine di adeguare i controlli successivi alla valutazione e gestione del rischio del sistema di fornitura.
Qualora siano già stati attuati adeguamenti del controllo a seguito della valutazione del rischio della fornitura conformemente, tra l’altro, alla parte C dell’allegato II della direttiva 98/83/CE, gli Stati membri possono prevedere la possibilità di confermare la loro validità senza richiedere il controllo a norma dei punti 2), lettera b) e 2), lettera c), per un altro periodo di almeno tre anni da punti rappresentativi dell’intera zona di fornitura.
Parte D
Metodi di campionamento e punti campionamento
1. I punti di prelievo dei campioni sono individuati in modo da garantire l’osservanza dell’articolo 6, paragrafo 1. Nel caso di una rete di distribuzione, ogni Stato membro può prelevare campioni nella zona di approvvigionamento o presso gli impianti di trattamento per particolari parametri se si può dimostrare che il valore ottenuto per i parametri in questione non sarebbe modificato negativamente. Nella misura del possibile, il numero di campioni deve essere equamente distribuito in termini di tempo e luogo.
2. Il campionamento al punto in cui i valori devono essere rispettati soddisfa gli obblighi seguenti:
a)
i campioni per verificare l’osservanza di obblighi relativi ad alcuni parametri chimici, in particolare rame, piombo e nichel, sono prelevati dal rubinetto dei consumatori senza prima far scorrere l’acqua. Occorre prelevare un campione casuale diurno pari a un litro. In alternativa, gli Stati membri possono utilizzare metodi che ricorrono al tempo fisso di ristagno e riflettono più precisamente le rispettive situazioni nazionali, come la dose settimanale media assunta dai consumatori, a condizione che, a livello di zona di approvvigionamento, ciò non rilevi un minor numero di casi di infrazione rispetto all’utilizzo del metodo casuale diurno;
b)
i campioni da utilizzare per verificare l’osservanza dei parametri microbiologici nel punto in cui i valori devono essere rispettati vanno prelevati in conformità della norma EN ISO 19458 (scopo B del campionamento).
3. I campioni per il controllo della Legionella nei sistemi di distribuzione domestici sono prelevati nei punti che rappresentano un rischio di proliferazione della Legionella, nei punti che rappresentano un’esposizione sistemica alla Legionella, o entrambi. Gli Stati membri elaborano orientamenti per i metodi di campionamento relativi alla Legionella.
4. Il campionamento presso la rete di distribuzione, ad eccezione che presso i rubinetti dei consumatori, deve essere conforme alla norma ISO 5667-5. Per i parametri microbiologici, i campionamenti presso la rete di distribuzione vanno effettuati e condotti in conformità della norma EN ISO 19458 (scopo A del campionamento).
1. Panoramica
| Titolo |
Regolamentazione |
|
1. Monitoring programmes established pursuant to Article 13(2) for water intended for human …
|
|
1.
|
Monitoring programmes established pursuant to Article 13(2) for water intended for human consumption shall:
|
(a)
|
verify that the measures in place to control risks to human health throughout the water supply chain from the abstraction area through treatment and storage to distribution are working effectively and that water intended for human consumption at the point of compliance is wholesome and clean;
|
|
(b)
|
provide information on the quality of water supplied for human consumption to demonstrate that the obligations set out in Article 4 and the parametric values set in accordance with Article 5 are being met;
|
|
(c)
|
identify the most appropriate means of mitigating the risk to human health.
|
|
|
|
2. Monitoring programmes established pursuant to Article 13(2) shall include one or a combination …
|
|
2.
|
Monitoring programmes established pursuant to Article 13(2) shall include one or a combination of the following:
|
(a)
|
collection and analysis of discrete water samples;
|
|
(b)
|
measurements recorded by a continuous monitoring process.
|
In addition, monitoring programmes may consist of:
|
(a)
|
inspections of records of the functionality and maintenance status of equipment;
|
|
(b)
|
inspections of the abstraction area, and of the treatment, storage and distribution infrastructure, without prejudice to monitoring requirements provided for under point (c) of the first subparagraph of Article 8(2) and point (b) of the first subparagraph of Article 10(1).
|
|
|
|
3. Monitoring programmes shall also include an operational monitoring programme that provides rapid …
|
|
3.
|
Monitoring programmes shall also include an operational monitoring programme that provides rapid insight into operational performance and water quality problems and that allows rapid pre-planned remedial action. Such operational monitoring programmes shall be supply-specific, taking into account the outcomes of the identification of hazards and hazardous events and the risk assessment of the supply system, and shall be intended to confirm the effectiveness of all control measures in abstraction, treatment, distribution and storage.
The operational monitoring programme shall include the monitoring of the parameter ‘turbidity at the water supply plant’ in order to regularly control the efficacy of physical removal by filtration processes, in accordance with the reference values and frequencies indicated in the following table (not applicable for groundwater sources where turbidity is caused by iron and manganese):
|
Operational parameter
|
Reference value
|
|
turbidity at the water supply plant
|
0,3 NTU in 95 % of samples and none to exceed 1 NTU
|
|
Volume (m3) of water distributed or produced each day within a supply zone
|
Minimum frequency of sampling and analysis
|
|
≤ 1 000
|
Weekly
|
|
> 1 000 to ≤ 10 000
|
Daily
|
|
> 10 000
|
Continuous
|
The operational monitoring programme shall also include the monitoring of the following parameters in raw water to control the efficacy of the treatment processes against microbiological risks:
|
Operational parameter
|
Reference value
|
Unit
|
Notes
|
|
Somatic coliphages
|
50 (for raw water)
|
Plaque Forming Units (PFU)/100 ml
|
This parameter shall be measured if the risk assessment indicates that it is appropriate to do so. If it is found in raw water at concentrations > 50 PFU/100 ml, it should be analysed after steps of the treatment train in order to determine log removal by the barriers in place and to assess whether the risk of a breakthrough of pathogenic viruses is sufficiently under control.
|
|
|
|
4. Member States shall ensure that monitoring programmes are reviewed on a continuous basis and …
|
|
4.
|
Member States shall ensure that monitoring programmes are reviewed on a continuous basis and updated or confirmed at least every six years.
|
Part B
Parameters and sampling frequencies
|
|
1. List of parameters Group A The following parameters (Group A) shall be monitored in accordance …
|
|
1.
|
List of parameters
Group A
The following parameters (Group A) shall be monitored in accordance with the monitoring frequencies set out in Table 1 of point 2:
|
(a)
|
Escherichia coli (E. coli), intestinal enterococci, coliform bacteria, colony count 22 °C, colour, turbidity, taste, odour, pH and conductivity;
|
|
(b)
|
other parameters identified as relevant in the monitoring programme, in accordance with Article 5(3) and, where relevant, through a risk assessment of the supply system as set out in Article 9 and Part C of this Annex.
|
Under specific circumstances, the following parameters shall be added to the Group A parameters:
|
(a)
|
ammonium and nitrite, if chloramination is used;
|
|
(b)
|
aluminium and iron, if used as water treatment chemicals.
|
Escherichia coli (E. coli) and intestinal enterococci are considered ‘core parameters’ and their monitoring frequencies shall not be the subject of a reduction due to a risk assessment of the supply system in accordance with Article 9 and Part C of this Annex. They shall always be monitored at least at the frequencies set out in Table 1 of point 2.
Group B
In order to determine compliance with all parametric values set out in this Directive, all other parameters not analysed under Group A and set in accordance with Article 5, except for parameters in Part D of Annex I, shall be monitored at least at the frequencies set out in Table 1 of point 2, unless a different sampling frequency is determined on the basis of a risk assessment of the supply system carried out in accordance with Article 9 and Part C of this Annex.
|
|
|
2. Sampling frequencies Table 1. Minimum frequency of sampling and analysis for compliance …
|
|
2.
|
Sampling frequencies
Table 1. Minimum frequency of sampling and analysis for compliance monitoring
|
Volume of water distributed or produced each day within a supply zone
(See Notes 1 and 2) m3
|
Group A parameter
number of samples per year
|
Group B parameter
number of samples per year
|
|
|
< 10
|
> 0 (See Note 4)
|
> 0 (See Note 4)
|
|
≥ 10
|
≤ 100
|
2
|
1 (See Note 5)
|
|
> 100
|
≤ 1 000
|
4
|
1
|
|
> 1 000
|
≤ 10 000
|
4 for the first 1 000 m3/d
+ 3 for each additional 1 000 m3/d and part thereof of the total volume
(See Note 3)
|
1 for the first 1 000 m3/d
+ 1 for each additional 4 500 m3/d and part thereof of the total volume
(See Note 3)
|
|
> 10 000
|
≤ 100 000
|
3 for first 10 000 m3/d
+ 1 for each additional 10 000 m3/d and part thereof of the total volume
(See Note 3)
|
|
> 100 000
|
|
12 for first 100 000 m3/d
+ 1 for each additional 25 000 m3/d and part thereof of the total volume
(See Note 3)
|
|
Note 1:
|
A supply zone is a geographically defined area within which water intended for human consumption comes from one or more sources and within which the water quality can be considered as being approximately uniform.
|
|
Note 2:
|
The volumes are calculated as averages taken over a calendar year. The number of inhabitants in a supply zone may be used instead of the volume of water to determine the minimum frequency, assuming water consumption of 200 l/(day*capita).
|
|
Note 3:
|
The frequency indicated is calculated as follows: e.g. 4 300 m3/d = 16 samples for Group A parameters (four for the first 1 000 m3/d + 12 for additional 3 300 m3/d).
|
|
Note 4:
|
For water suppliers, where an exemption has not been granted under point (b) of Article 3(3), Member States shall lay down the minimum sampling frequency for parameters of Groups A and B, provided that core parameters are monitored at least once per year.
|
|
Note 5:
|
Member States may reduce the sampling frequency, provided that all parameters set in accordance with Article 5 are monitored at least once every six years and are monitored in cases where a new water source is integrated into the water supply system or changes to that system, as a result of which a potentially adverse effect on the quality of water is to be expected, are made.
|
|
|
Part C
Risk assessment and risk management of the supply system
|
|
1. Based on the outcome of the risk assessment of the supply system as referred to in Article 9 …
|
|
1.
|
Based on the outcome of the risk assessment of the supply system as referred to in Article 9, the list of parameters considered in the monitoring shall be extended and the sampling frequencies set out in Part B increased where any of the following conditions is fulfilled:
|
(a)
|
the list of parameters or frequencies set out in this Annex is not sufficient to fulfil the obligations imposed under Article 13(1);
|
|
(b)
|
additional monitoring is required for the purposes of Article 13(5);
|
|
(c)
|
it is necessary to provide the assurances set out in point (a) of point 1 of Part A;
|
|
(d)
|
increasing the sampling frequencies is necessary pursuant to point (a) of the first subparagraph of Article 8(4).
|
|
|
|
2. As a result of a risk assessment of the supply system, the list of parameters considered in the …
|
|
2.
|
As a result of a risk assessment of the supply system, the list of parameters considered in the monitoring and the sampling frequencies set out in Part B may be reduced provided that all of the following conditions are met:
|
(a)
|
the location and frequency of sampling is determined in relation to the parameter’s origin, as well as the variability of, and long-term trend regarding, its concentration, taking into account Article 6;
|
|
(b)
|
as regards reducing the minimum sampling frequency of a parameter, the results obtained from samples collected at regular intervals over a period of at least three years, from sampling points representative of the whole supply zone, are all less than 60 % of the parametric value;
|
|
(c)
|
as regards removing a parameter from the list of parameters to be monitored, the results obtained from samples collected at regular intervals over a period of at least three years, from sampling points representative of the whole supply zone, are all less than 30 % of the parametric value;
|
|
(d)
|
as regards removing a parameter from the list of parameters to be monitored, the decision is based on the outcome of the risk assessment that takes into account the results of monitoring of sources of water intended for human consumption and confirms that human health is protected from the adverse effects of any contamination of water intended for human consumption, as laid down in Article 1;
|
|
(e)
|
as regards reducing the sampling frequency of a parameter or removing a parameter from the list of parameters to be monitored, the risk assessment confirms that no factor that can be reasonably anticipated is likely to cause deterioration of the quality of the water intended for human consumption.
|
Where monitoring results, demonstrating that the conditions set out in points (2)(b) to (2)(e) are met, are already available by 12 January 2021, those monitoring results may, from that date, be used to adapt the monitoring following the risk assessment of the supply system.
Where adjustments of monitoring have already been implemented following risk assessment of the supply system in accordance, inter alia, with Part C of Annex II of Directive 98/83/EC, Member States may provide for the possibility to confirm their validity without requiring monitoring in accordance with point 2(b) and 2(c) over a further period of at least three years from points representative of the whole supply zone.
|
Part D
Sampling methods and sampling points
|
|
1. Sampling points shall be determined so as to ensure compliance with Article 6(1). In the case of …
|
|
1.
|
Sampling points shall be determined so as to ensure compliance with Article 6(1). In the case of a distribution network, a Member State may take samples within the supply zone or at the treatment works for particular parameters if it can be demonstrated that there would be no adverse change to the measured value of the parameters concerned. As far as possible, the number of samples shall be distributed equally in time and location.
|
|
|
2. Sampling at the point of compliance shall meet the following requirements: (a) compliance …
|
|
2.
|
Sampling at the point of compliance shall meet the following requirements:
|
(a)
|
compliance samples for certain chemical parameters, in particular copper, lead, and nickel, shall be taken at the consumers’ tap without prior flushing. A random daytime sample of one litre volume is to be taken. As an alternative, Member States may use fixed stagnation time methods that better reflect their national situation, such as the average weekly intake by consumers, provided that, at the supply zone level, this does not result in fewer cases of non-compliance than using the random daytime method;
|
|
(b)
|
compliance samples for microbiological parameters at the point of compliance shall be taken and handled in accordance with EN ISO 19458, sampling purpose B.
|
|
|
|
3. Samples for Legionella in domestic distribution systems shall be taken at risk points for …
|
|
3.
|
Samples for Legionella in domestic distribution systems shall be taken at risk points for proliferation of Legionella, points representative for systemic exposure to Legionella, or both. Member States shall establish guidelines for sampling methods for Legionella.
|
|
|
4. Sampling in the distribution network, with the exception of sampling at the consumers’ tap …
|
|
4.
|
Sampling in the distribution network, with the exception of sampling at the consumers’ tap, shall be in accordance with ISO 5667-5. For microbiological parameters, samples in the distribution network shall be taken and handled in accordance with EN ISO 19458, sampling purpose A.
|
|
,
1.1 Riferimenti
1.2 Requisiti identificati
1.3 Standard correlati
2. Requisiti identificati
Requisiti
| Fonte |
Requisito |
3. Standard correlati
- Builddate: 23.12.2020 00:00:00 -Doknr: CELEX:32020L2184
- EULAW -
EN: Legal acts of the European Union from EUR-Lex, https://eur-lex.europa.eu/. © European Union. Re-use is authorised by Decision 2011/833/EU, provided the source is acknowledged; the consolidated texts are licensed under CC BY 4.0 (EUR-Lex legal notice). Divided into sections and converted into the GRCA format, the wording unchanged. Only the legislation published in the Official Journal of the European Union is deemed authentic.
DE: Rechtsakte der Europäischen Union aus EUR-Lex, https://eur-lex.europa.eu/. © Europäische Union. Weiterverwendung nach Beschluss 2011/833/EU mit Quellenangabe gestattet; die konsolidierten Fassungen stehen unter CC BY 4.0 (Rechtlicher Hinweis von EUR-Lex). In Abschnitte aufgeteilt und in das GRCA-Format umgewandelt, der Wortlaut unverändert. Verbindlich sind allein die im Amtsblatt der Europäischen Union veröffentlichten Rechtsakte.
|